MSX-W13-IN-LCD | Differential pressure transmitter | wall mount | universal current/voltage outputs | uni-directional | range 3 (10 | 15 | 25 | 28
$0.00
Get your Special Pricing!
Log In / Create an Account for the LOWEST PRICING on our most Popular Brands!
Brand: Dwyer InstrumentsSKU: MSX-W13-IN-LCD
Availability: Get a Quote
The product is not cancelable or returnable unless found defective

Speak With a Technical Expert

Call (847) 773-1023

Hours: 9am - 5pm CDT M-F

MSX-W13-IN-LCD | Differential pressure transmitter | wall mount | universal current/voltage outputs | uni-directional | range 3 (10 | 15 | 25 | 28" wc) with LCD display. | Dwyer Instruments

Dwyer Instruments | MSX-W13-IN-LCD
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to MSX-W13-IN-LCD

Overview

Details for MSX-W13-IN-LCD

Accurately Measure Pressure Differentials with Dwyer Instruments MSX-W13-IN-LCD Wall Transmitter Dwyer Instruments MSX-W13-IN-LCD Wall Transmitter is engineered to provide precise pressure differential measurements in various industrial applications. This versatile transmitter features a wide measurement range of 10 to 28 inches of water column, making it ideal for monitoring air pressure, flow, and level in HVAC systems, cleanrooms, and laboratories. Its durable construction ensures reliable operation in demanding environments. The MSX-W13-IN-LCD Wall Transmitter is user-friendly, with a large, easy-to-read LCD display that provides clear readings. Its intuitive keypad allows for quick and convenient setup and configuration, while the included mounting bracket simplifies installation. With its accuracy and reliability, the MSX-W13-IN-LCD Wall Transmitter is essential for industrial engineers and maintenance professionals seeking a dependable solution for pressure differential measurement. Key Features and Benefits: Accurate and reliable pressure differential measurement Wide measurement range of 10 to 28 inches of water column Easy-to-read LCD display Intuitive keypad for simple setup Durable construction for long-lasting operation Included mounting bracket for hassle-free installation Trust our HVAC supply store for your industrial needs and benefit from competitive prices and fast shipping!

Series MSX Magnesense® Differential Pressure Transmitter

Monitors Differential Pressure, Air Velocity and Volumetric Flow

The Series MSX Magnesense® Differential Pressure Transmitter combines the stability and versatility of the original Series MS2 Magnesense® II transmitter for use in building control applications. The MSX simplifies the ordering process to deliver the desired configuration, which reduces product setup time. Pressure ranges are available in Pa, mm w.c., and in w.c. All pressure ranges can be configured in unidirectional or bidirectional modes, providing a total of 32 ranges. The MSX transmitter can provide a linear pressure output or a linear velocity output with the square root extraction from the transmitter. Additional parameters have been included to expand the square root capability for calculating flow. Dual voltage and milliamp output signals can be used to provide both control and equipment output signal verification.

NIST CALIBRATION available in Product Configurator.

Product Applications

    • Filter monitoring in air handler units
    • Building pressure in pharmaceutical/semiconductor clean rooms
    • Duct static pressure in commercial buildings
    • Air velocity/flow in VAV systems
 
 

 

  • Read LCD values easier with rotatable 180° display
  • Quick and easy wiring via the optional toolless terminal block
  • Add safety to variety of applications with UL94 V-0 and plenum ratings

Specifications

Series
MSX Magnesense® Differential Pressure Transmitter
Service
Air and non-combustible; compatible gases.
Wetted Materials
Consult factory.
Accuracy
±1% FSO.
Stability
±1% FSO/year.
Temperature Limits
-4 to 158°F (-20 to 70°C).
Pressure Limits
Ranges 0 and 1: 3.6 psi max operation; 6 psi burst; Ranges 2; 3 and 4: 6 psi max operation; 6 psi burst.
Power Requirements
10-36 VDC (2-wire); 17-36 VDC or isolated 21.6-33 VAC (3-wire).
Output Signals
4-20 mA (2-wire); 0-10 V or 0-5 V selectable (3-wire).
Response Time
Instantaneous (default) or 3 s (selectable).
Zero and Span Adjustments
Digital push-button.
Loop Resistance
Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 k Ω.
Current Consumption
21 mA max continuous.
Electrical Connections
4-wire removable European style terminal block for 16 to 26 AWG.
Electrical Entry
1/2" NPS thread.
Display (optional)
4 digit LCD.
Process Connections
1/8"; 3/16"; 1/4"; 5 mm; and 6 mm ID flexible tubing.
Enclosure Rating
NEMA 4X (IP66); UL 2043 (Plenum); UL94 V-0.
Mounting Orientation
Pressure sensor measurement unaffected by orientation.
Weight
8.0 oz (230 g).
Agency Approvals
CE.

Reviews

People Also Searched

MSX-W13-IN-LCD
Dwyer Instruments MSX-W13-IN-LCD
MSX W13 IN LCD
MSXW13INLCD
Dwyer Instruments MSX W13 IN LCD
Dwyer Instruments MSXW13INLCD
MSX-W13-IN-LCD price
Dwyer Instruments MSX-W13-IN-LCD price
MSX W13 IN LCD price
MSXW13INLCD price
Dwyer Instruments MSX W13 IN LCD price
Dwyer Instruments MSXW13INLCD price